ACE Home Inspections, LLC

P.O. Box 1993
Alabaster, AL 35007
(205)401-3030

Customer
Sample

Home
Sample

Real Estate Agent
Sample

Inspection Date 
Wednesday, October 24, 2007
Weather:
Cloudy
Report ID:
07030 FINAL REPORT
Temperature:
65 to 70 degrees
Inspected By 
Jeff Aiken

SUMMARY


ACE Home Inspections, LLC

P.O. Box 1993
Alabaster, AL 35007
(205)401-3030

Customer
Sample

Home
Sample

The following items or discoveries indicate that these systems or components do not function as intended or adversely affects the habitabilty of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation.

This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of the home.

This Summary is not the entire report. The complete report may include additional information of concern to the customer. It is recommended that the customer read the complete report.

WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS
1.1 WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-The water meter basin is located at the street beside the driveway entrance. The soil or ground around the recessed basin is low where the sides are partially visible where additional soil or landscaping completion is recommended. This is an aesthetic issue which does not effect overall functionality or operation.
1.2 WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
It is always recommended that soil against all foundation walls be sloped gently down and away for proper drainage. This prevents water from draining down along the foundation. The numbers correspond to the appropriate pictures.

1,2,3,4,5,6,7,8,9,10,11,12,13,14-The house has been constructed on the side of a modest hill where all water drains down to the far right wooded area. There is a sunken area or trench along the front, rear, and right foundation walls, where the tops of the concrete footer are exposed. These low areas have caused water draining down from the left to settle against and seep through into the crawlspace based on the darker discolored areas of dampness and/or moisture observed on the interior walls and ground. Owner stated exact new owner landscaping desires are unknown where plans are to perform all needed landscaping at one time after discussing with new owner, so as to be able to minimize backhoe expenses. The soil directly against the left wall slopes gently down and away, however water from the left drains directly down and towards this wall where the installation of a wide shallow v-shaped drainage depression, parallel with the wall, is highly recommended. Depressions such as this can be planted with grass and are simply just part of the yard and are barely noticeable, however play a key role in directing water away from the wall and off to the far sides.

After landscaping has been completed, recommend monitoring during a storm and further investigation by a licensed landscaping contractor if any drainage issues such as sizeable collections should develop, especially near or against the foundation. Repairs or drainage enhancements at that time may include but are not limited to additional compacted soil in any low areas or a more profound wide shallow v-shaped drainage depression.

ACE Home Inspections, LLC is not responsible for any drainage issues that may be uncovered during a future storm because it was not raining at time of the inspection and any conclusions are based solely on only what was inspected. Repair or drainage enhancement ideas are listed only as a courtesy and does not always infer that an actual problem exists where further investigation during a storm and by a licensed landscaping contractor(s) or engineer(s) along with any repairs deemed necessary, are always recommended. ACE Home Inspections, LLC is not a licensed landscaping contractor or engineer and has no intent to supercede any of their conclusions and since opinions may vary it is always recommended, especially in any situations of disagreement, that multiple licensed landscaping contractors or engineers be contacted for an opinion.

PORCHES, DECKS, PATIOS, STEPS, STAIRS, RAILINGS, BANISTERS
2.0 PORCHES, DECKS, PATIOS, STEPS, STAIRS, RAILINGS, BANISTERS
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3-The bottom of the banisters along the porch steps have some wobble because the two bottom 4x4 wood posts have been attached only to the sides of the stringers. Present construction is adequate however may continue to loosen over time where a more robust type construction is always recommended, but is NOT required. Strengthening may include but is not limited to removal of the two bottom 4x4 wood posts and installation of two new 4x4 wood posts secured in concrete footers along with a small poured concrete slab bottom step or landing area.
2.1 PORCHES, DECKS, PATIOS, STEPS, STAIRS, RAILINGS, BANISTERS
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-The front porch and rear deck "Deck Band joists" are toed in with only nails and are NOT attached properly to the wall or band of home with 5/8 galvanized "Lag Screws" or "Carriage Bolts" approximately every 36 inches. Even if determined not to be required in the jurisdiction where the house is constructed, a proper and ROBUST porch and deck attachment is always recommended for safety reasons.

EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
3.4 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2-The front and rear entry door deadbolt striker holes are NOT deep enough, preventing the deadbolt from fully becoming engaged. A deadbolt that is not fully engaged in the out position, poses a security issue and can sometimes be readily opened with a knife or screwdriver. It is recommended that the striker holes be made deeper by carefully using a small drill bit. (security issue)
3.5 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-Weatherstripping along the front and rear entry door frames is missing and is always recommended.
3.6 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-Entry door wood framing and outer trim boards have been covered with aluminum. This is good, however it is always recommended that the lower edges be slightly above and not touch the threshold or be heavily caulked if they do make contact because they can absorb water and become deteriorated over time. All entry door framing boards are flush with the threshold where clear silicone caulking is recommended.
3.7 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-There are gaps around the piping from the exterior located air conditioner condenser unit where it pierces the right wall. Recommend filling gaps with clear silicone caulking or mortar.
3.8 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-There are gaps around the PVC drain pipe from the crawlspace located air conditioner evaporator coils where it pierces the rear wall. Recommend filling gaps with clear silicone caulking or mortar.
3.9 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-There is a small gap between the rear wall dryer vent cover and the siding where clear silicone caulking along the top is recommended.
3.10 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The front entry door is difficult to close because the top side rubs or hits against the door frame. This appears to be from the hinges being loose where repair for a smoother closing is recommended.

ATTIC, ROOF INTERIOR
4.5 ATTIC, ROOF INTERIOR
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-The hallway attic entry scuttle hole does not cete down flush in place because of two nails where nail removal is recommended.
4.6 ATTIC, ROOF INTERIOR
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The exhaust fan in each bathroom was found to be completely covered with insulation where they do NOT terminate properly to the exterior. Exhaust vents that terminate into the attic can cause excess moisture/humidity within the attic and possibly lead to moisture damaged ceiling plasterboard. A vinyl or metal flex hose can be ran from each fan to the closest gable or soffit vent. These kits are rather inexpensive and can be purchased at major home centers and are always recommended.

KITCHEN, BATHROOMS, INTERIOR ROOMS
5.6 KITCHEN, BATHROOMS, INTERIOR ROOMS
MISCELLANEOUS INFORMATION
The stove and oven unit has excessive wobble where proper leveling or balancing to floor is recommended.
5.7 KITCHEN, BATHROOMS, INTERIOR ROOMS
MISCELLANEOUS INFORMATION
The refrigerator has excessive wobble where proper leveling or balancing to floor is recommended.
5.8 KITCHEN, BATHROOMS, INTERIOR ROOMS
MISCELLANEOUS INFORMATION
The living room ceiling fan has noticeable wobble on high speed where proper alignment or balancing is recommended.
5.9 KITCHEN, BATHROOMS, INTERIOR ROOMS
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-The electrical receptacle to the right of the kitchen sink and another on the right exterior wall within the master bedroom are loose where they move around whenever a plug is inserted or removed. recommend both be properly secured where movement is prohibited.

PLUMBING (Main, Exterior, Water Heater, Washer, Dryer)
6.6 PLUMBING SYSTEM
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2-Both exterior hose bibs are missing a bacflow preventer. They are relatively inexoensive and can be purchase at major home centers. Even if determined not to be required in the jurisdiction where the house is constructed, they are always recommended for safety reasons.

ADDITIONAL BACFLOW PREVENTER INFORMATION:

1-The simplest backflow protection is the simple air gap between the end of a sink faucet where the water exits and the flood rim of the sink as explained in the bathroom section. Another place where backflow protection is needed is on outside hose bibs or faucets. This involves purchasing a relatively inexpensive backflow preventer that easily screws on to the end of the faucet that will allow water to flow in only one direction, out of your faucet. This prevents any contaminated water in your hose from being sucked back through the house water supply. It is recommended that all hose bibs have a backflow preventer such as one shown in picture 2.
6.7 PLUMBING SYSTEM
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The water heater side mounted TPR valve does not have a 3/4 inch sized extension pipe ran to within 6 inches of the floor. Extension pipes are always recommended for all water haters, wherever they are located. (safety)

ADDITIONAL TPR VALVE INFORMATION:

Water heaters have a TPR valve (Temperature Pressure Relief) or T&P valve, which is a safety device that releases pressure if the pressure or the temperature reach an unsafe level. All tank type units must have a TPR valve, otherwise they could blow up. The purpose of the TPR valve is to provide an important safety mechanism that allows for the immediate discharge of excess temperature and pressure that builds up inside the tank as the water is heated. Due to the scalding potential of the discharge from the TPR valve, the outlet from the valve should be piped to a safe area. Typically TPR valve discharges are piped down to within 6 inches of the floor or outside of the dwelling at near ground level. A TPR Valve that has been fitted with a discharge pipe that is smaller than the size of the valve outlet is a common defect that is strictly prohibited because smaller discharge pipes restrict the flow of the pressurized water released by the valve. This creates a dangerous bottleneck, building-up even more pressure at the point of discharge that can cause the tank to explode. Personal injury (or death) and property damage may result. The discharge pipe must be made of a material that's rated for both high temperature and pressure. This includes most rigid wall copper, iron and, in most places, chlorinated polyvinylchloride (CPVC plastic not regular PVC) pipe. The pipe size must match the opening size of the TPR valve discharge (usually : inch). It must terminate 6"-12" above the floor, and the end cannot be threaded or have a fitting which permits connecting a plug or cap.

ELECTRICAL (Service, Interior Distribution Panels, Exterior)
7.5 ELECTRICAL SYSTEM
MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3-All outlets were tested with a SureTest outlet tester and found to have proper voltage and grounding. GFCI protected outlets were observed in bathrooms, kitchen, and exterior outlets. This is good!

(GFCI issue) The rear deck is GFCI protected through the left side hallway bathroom GFCI type outlet. The front porch outlets are GFCI protected through the master bathroom GFCI type outlet. This is functional, however is no longer an acceptable new construction method where all bathrooms outlets should have their own isolated GFCI protection, and all kitchen outlets within six feet of a sink basin should have their own isolated GFCI protection. Only exterior, garage and basement outlets are allowed to still be tied together with the same GFCI protection. This may not be required within the jurisdiction where the house was constructed, where builder may not be required to isolate, however is always recommended.

(AFCI issue) Since this house was constructed after January 1, 2002 it is required by the National Electrical Code to have proper AFCI protected bedroom outlets. Normally each bedroom will have an AFCI type breaker in the electrical panel that has a green or blue reset button. No AFCI protection was observed at time of the inspection. These may not be required within the jurisdiction where the house was constructed, where builder may not be required to install, however are always recommended.

Opinions by licensed electrical contractors on this issue may vary where contacting. There are hundreds of various jurisdictions throughout the state of Alabama. The knowing of each's specific rules or codes is beyond the scope of the inspection, where the contacting of the local jurisdiction is always recommended, and correcting if required.

Remember that breakers are only designed to protect the wiring, while a GFCI and AFCI are designed to protect you!

GENERAL GFCI AND AFCI INFORMATION:

A GFCI or Ground-Fault-Circuit Interrupter is a device intended for the protection of personnel that functions to de-energize a circuit within an established period of time when a current to ground exceeds the values established for a Class A device. Class A ground-fault circuit interrupters trip when the current to ground has a value in the range of 4ma (milli-amps) to 6ma (milli-amps). All outlets within 6 feet of any water source, whirlpool tubs, hot tubs, swimming pools, unfinished basement or crawlspace, exterior, and garage outlets should always be properly GFCI protected.

Starting January 1, 2002, The National Electrical Code, Section 210-12, requires that all branch circuits supplying 125 volts, single phase, 15 and 20 ampere outlets installed in bedrooms be protected by an arc-fault circuit interrupter. They may eventually be required elsewhere, but for now just in bedrooms because a CPSC study showed many home fire deaths were related to bedroom circuits. The AFCI - arc-fault-circuit-interrupter will shut off a circuit in a fraction of a second if arcing develops. The current inside of an arc is not always high enough to trip a regular breaker.

There is a difference between AFCIs and GFCIs. AFCIs are intended to reduce the likelihood of fire caused by electrical arcing faults: whereas, GFCIs are personnel protection intended to reduce the likelihood of electric shock hazard.

7.6 ELECTRICAL SYSTEM
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The rear deck outlet receptacle and another to the left of the front entry door are missing an exterior weatherproof type cover. (safety)

FOUNDATION INTERIOR
10.4 BASEMENT, CRAWLSPACE, FOUNDATION INTERIOR
MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-The crawlspace vent opening covers are laying on the ground where installation is recommended to keep small animals from entering.

ACE Home Inspections, LLC

Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value of the property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system that was not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties or guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area or perform any procedure that may damage the property or its components or be dangerous to the home inspector or other persons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or component that does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or remove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.

ACE Home Inspections, LLC

Prepared Using HomeGauge http://www.homegauge.com/ SHGI (c) 2000-2003 : Licensed To Jeffrey James Aiken

 

WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS

Styles & Materials
LANDSCAPING:
PROPERTY SLOPES DOWN TO RIGHT
ALL WATER DRAINS TO RIGHT
RETAINING WALLS:
NONE
WALKWAYS AND DRIVEWAYS:
LONG GRAVEL DRIVEWAY



Inspection Items
1.0 WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS
Comments: MISCELLANEOUS INFORMATION
1-The yard has not been seeded or planted with sod because the overall landscaping plan has yet to be finalized. Refer to report section 1.2 for additional information.
1.1 WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-The water meter basin is located at the street beside the driveway entrance. The soil or ground around the recessed basin is low where the sides are partially visible where additional soil or landscaping completion is recommended. This is an aesthetic issue which does not effect overall functionality or operation.
1.2 WALKWAYS, DRIVEWAYS, LANDSCAPING, RETAINING WALLS
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Picture 12
Picture 13
Picture 14
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
It is always recommended that soil against all foundation walls be sloped gently down and away for proper drainage. This prevents water from draining down along the foundation. The numbers correspond to the appropriate pictures.

1,2,3,4,5,6,7,8,9,10,11,12,13,14-The house has been constructed on the side of a modest hill where all water drains down to the far right wooded area. There is a sunken area or trench along the front, rear, and right foundation walls, where the tops of the concrete footer are exposed. These low areas have caused water draining down from the left to settle against and seep through into the crawlspace based on the darker discolored areas of dampness and/or moisture observed on the interior walls and ground. Owner stated exact new owner landscaping desires are unknown where plans are to perform all needed landscaping at one time after discussing with new owner, so as to be able to minimize backhoe expenses. The soil directly against the left wall slopes gently down and away, however water from the left drains directly down and towards this wall where the installation of a wide shallow v-shaped drainage depression, parallel with the wall, is highly recommended. Depressions such as this can be planted with grass and are simply just part of the yard and are barely noticeable, however play a key role in directing water away from the wall and off to the far sides.

After landscaping has been completed, recommend monitoring during a storm and further investigation by a licensed landscaping contractor if any drainage issues such as sizeable collections should develop, especially near or against the foundation. Repairs or drainage enhancements at that time may include but are not limited to additional compacted soil in any low areas or a more profound wide shallow v-shaped drainage depression.

ACE Home Inspections, LLC is not responsible for any drainage issues that may be uncovered during a future storm because it was not raining at time of the inspection and any conclusions are based solely on only what was inspected. Repair or drainage enhancement ideas are listed only as a courtesy and does not always infer that an actual problem exists where further investigation during a storm and by a licensed landscaping contractor(s) or engineer(s) along with any repairs deemed necessary, are always recommended. ACE Home Inspections, LLC is not a licensed landscaping contractor or engineer and has no intent to supercede any of their conclusions and since opinions may vary it is always recommended, especially in any situations of disagreement, that multiple licensed landscaping contractors or engineers be contacted for an opinion.
1.3 WALKWAYS, DRIVEWAYS, PATIOS, LANDSCAPING, RETAINING WALLS (Visible condition. Checking for proper water runoff away from the house, the landscape for presence of holes, sunken areas, bald spots, eroding areas, and tripping hazards, trees and vegetation clearances, and drainage weep holes or drains at the base of retaining walls.)
Comments: INSPECTED

PORCHES, DECKS, PATIOS, STEPS, STAIRS, RAILINGS, BANISTERS

Styles & Materials
FRONT PORCH:
RECESSED UNDER HOUSE ROOF
VINYL COVERED CEILING
6X6 WOOD ROOF SUPPORTS
DECK STYLE CONSTRUCTION
6X6 WOOD DECK POSTS
2X8 WOOD FLOOR JOISTS
SPACED 16 INCHES APART
REAR DECK:
NO ROOF
2X8 WOOD FLOOR JOISTS
SPACED 16 INCHES APART
4X4 WOOD DEC POSTS
STEPS AND STAIRWAYS:
2 SETS WOOD PORCH STEPS
WOOD DECK STEPS
RAILINGS AND BANISTERS:
WOOD BANISTERS
WITH PICKETS



Inspection Items
2.0 PORCHES, DECKS, PATIOS, STEPS, STAIRS, RAILINGS, BANISTERS
Picture 1
Picture 2
Picture 3
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3-The bottom of the banisters along the porch steps have some wobble because the two bottom 4x4 wood posts have been attached only to the sides of the stringers. Present construction is adequate however may continue to loosen over time where a more robust type construction is always recommended, but is NOT required. Strengthening may include but is not limited to removal of the two bottom 4x4 wood posts and installation of two new 4x4 wood posts secured in concrete footers along with a small poured concrete slab bottom step or landing area.
2.1 PORCHES, DECKS, PATIOS, STEPS, STAIRS, RAILINGS, BANISTERS
Picture 1
Picture 2
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-The front porch and rear deck "Deck Band joists" are toed in with only nails and are NOT attached properly to the wall or band of home with 5/8 galvanized "Lag Screws" or "Carriage Bolts" approximately every 36 inches. Even if determined not to be required in the jurisdiction where the house is constructed, a proper and ROBUST porch and deck attachment is always recommended for safety reasons.
2.2 PORCH (Visible condition of roof, eaves, gutters, attic, ventilation, columns, foundation, floor, coverings, storage closets.)
Comments: INSPECTED
2.3 PORCH (Visible condition and operation of doors, lights, switches, and outlets.)
Comments: INSPECTED
2.4 DECK (Visible condition. Checking roof, roof support structures, attic, ceilings, screens, gates, doors, if deck support columns are resting on concrete footers, and if deck is secured properly with lag bolts or a ledgerboard with metal joist brackets.)
Comments: INSPECTED
2.5 COMMON HALLWAYS AND CORRIDORS (Visible condition and operation of windows, doors, floors, cabinets, lights, switches, outlets, heating, cooling.)
Comments: INSPECTED
2.6 STOOPS, STEPS, STAIRS, BANISTERS, AND RAILINGS (Visible condition. Checking for potential tripping hazards from variations in step riser heights, narrow tread steps, unlevel steps or steep stairs. Checking for adequate headroom.)
Comments: INSPECTED
2.7 SPACINGS BETWEEN ANY TWO RAILING BANISTERS OF 4 TO 5 INCHES OR LESS (Safety issue for children.)
Comments: INSPECTED

EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY

Styles & Materials
DOOR INFO:
BOTH HAVE DEADBOLT
NO STORM DOORS
HOUSE WINDOWS:
VINYL
VINYL SASHES
SINGLE-HUNG
DOUBLE-PANE
SIDING MATERIAL:
VINYL LAP BOARDS
SOFFIT/FASCIA MATERIAL:
VINYL AND ALUMINUM
GUTTER MATERIAL:
ALUMINUM
FOUNDATION MATERIAL:
CONCRETE BLOCK
EXTERIOR MORTAR SWISHED
VIEWED ROOF FROM:
GROUND (binoculars)
ROOF TYPE:
MAIN IS GABLE TYPE
FRONT PERPENDICULAR GABLE
ROOF COVERING:
FIBERGLASS ASPHALT SHINGLES
LAYERS:
ONE
ROOF PENETRATIONS:
4 TOTAL PIERCE ROOF
ESTIMATED ROOF AGE:
NEW
ROOF VENTILATION:
GABLE VENTS
SOFFIT VENTS
1 WIND TURBINE
CHIMNEY(S):
NONE
SKY LIGHT (S):
NONE
HOUSE DIMENSIONS:
47FT WIDE X 30FT DEEP



Inspection Items
3.0 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Comments: FOR YOUR INFORMATION
House siding is vinyl, soffit and fascia are covered with vinyl and aluminum, entry door framing is covered with aluminum all of which are relatively low maintenance. This is good!

Any exposed exterior wood is subject to deterioration if not properly maintained. It is strongly recommended that all exterior wood be painted on a periodic basis. The whole point is to prevent moisture damage which leads to costly total replacement. The bottom six to twelve inches of wood door frames (not covered with aluminum) are notorious for rapid deterioration when not properly maintained. It is very important to at least once a year, and more if needed, to keep at least the bottom six to twelve inches caulked and painted. IT CAN NOT BE STRESSED ENOUGH THAT PERIODIC PAINTING OF ALL WOOD SURFACES IS A MUST!!! Whenever small cracks start to develop at the end of the boards, it is time to paint! (Maintenance tip.)
3.1 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Picture 3
Picture 4
Comments: FOR YOUR INFORMATION
1,2,3,4-The roof covering and flashing appear adequate with no loose or missing areas. This is good!
3.2 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Comments: MISCELLANEOUS INFORMATION
1-Once landscaping is complete and grass is present, a splashblock under or vinyl extension to the bottom of all gutter downspouts is always recommended to help direct water away from the foundation walls. These are inexpensive and can be purchased at major home centers. (Maintenance tip.)
3.3 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Comments: MISCELLANEOUS INFORMATION
1,2,3,4,5,6-The concrete block foundation walls are relatively level and free of major cracking. There is one 4 foot vertical hairline wide crack located under the right side of the front entry door. This crack travels all the way through where it is also noticeable on the interior side within the crawlspace. There is no side-to-side differential where both sides are even and one side is NOT out further than the other, indicating there has been no shifting and this most likely was caused from normal settlement and should not pose an issue unless it continues to worsen with time. Periodic monitoring is recommended.
3.4 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2-The front and rear entry door deadbolt striker holes are NOT deep enough, preventing the deadbolt from fully becoming engaged. A deadbolt that is not fully engaged in the out position, poses a security issue and can sometimes be readily opened with a knife or screwdriver. It is recommended that the striker holes be made deeper by carefully using a small drill bit. (security issue)
3.5 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-Weatherstripping along the front and rear entry door frames is missing and is always recommended.
3.6 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Picture 1
Picture 2
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-Entry door wood framing and outer trim boards have been covered with aluminum. This is good, however it is always recommended that the lower edges be slightly above and not touch the threshold or be heavily caulked if they do make contact because they can absorb water and become deteriorated over time. All entry door framing boards are flush with the threshold where clear silicone caulking is recommended.
3.7 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-There are gaps around the piping from the exterior located air conditioner condenser unit where it pierces the right wall. Recommend filling gaps with clear silicone caulking or mortar.
3.8 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-There are gaps around the PVC drain pipe from the crawlspace located air conditioner evaporator coils where it pierces the rear wall. Recommend filling gaps with clear silicone caulking or mortar.
3.9 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-There is a small gap between the rear wall dryer vent cover and the siding where clear silicone caulking along the top is recommended.
3.10 EXTERIOR DOORS, WINDOWS, SIDING, FOUNDATION, GUTTERS, ROOF, CHIMNEY
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The front entry door is difficult to close because the top side rubs or hits against the door frame. This appears to be from the hinges being loose where repair for a smoother closing is recommended.
3.11 WINDOWS, SHUTTERS AND AWNINGS (Visible condition and checking for the presence and functionality of window flashing and operation of windows and window locks.)
Comments: INSPECTED
3.12 ENTRY DOORS, STORM DOORS, SECURITY DOORS, AND DOORBELL (Visible condition and operation, checking hardware, locks, coverings, frame, trim, weatherstripping, presence of deadbolts on all exterior doors, proper locking, opening, and closing of sliding glass doors, and the presence of a security dead-pin in all sliding glass doors.)
Comments: INSPECTED
3.13 FOUNDATION WALLS AND MORTAR JOINTS (Visible condition, checking for cracked, crumbled, loose, missing, eroded areas, or large gaps)
Comments: INSPECTED
3.14 EXTERIOR WALL COVERINGS, FLASHING,TRIM, AND CAULKING (Visible condition. A wall flashing is defined as a material used around angles or junctions on exterior walls to prevent water leakage.)
Comments: INSPECTED
3.15 HOUSE FRAMING (Visible condition, checking for any cracks developing outside of the house, cracks between a chimney and the exterior wall or any cracks running outward at an angle from the upper corners of windows and door frames.)
Comments: INSPECTED
3.16 OUTSIDE ACCESS TO HOUSE IS RODENT PROOF
Comments: INSPECTED
3.17 ROOF COVERING (Visible condition. Checking roof penetrations such as, roof vents, ridge vents, wind turbines, soffit vents, gable vents, chimneys, furnace flues, water heater flues, plumbing vents, skylights and any other penetrations. Checking flashings which are used to seal around roof penetrations and intersections. Checking rain caps on chimneys and flues.)
Comments: INSPECTED
3.18 SOFFIT, FASCIA, EAVES, GUTTERS, DOWNSPOUTS (Visible condition. Checking if gutters are provided where necessary, including porches, flat roofs, and dormers. Checking whether splasblocks are in place if underground piping is not used for rain gutter drainage.)
Comments: INSPECTED

ATTIC, ROOF INTERIOR

Styles & Materials
ROOF STRUCTURE:
2 x 6 WOOD RAFTERS
PRESSED WOOD ROOF DECKING
COLLAR-TIE BRACING BOARDS
PURLIN BRACING BOARDS
CEILING STRUCTURE:
2 x 6 WOOD JOISTS
RAFTER SPACING:
24 INCHES
JOIST SPACING:
24 INCHES
INSULATION TYPE:
FIBERGLASS
INSULATION INCHES:
12 INCHES
R- VALUE:
R-30
ATTIC INFO:
HIGH CLEARANCE ATTIC
NO DECKING FOR STORAGE
1 SWITCHED LIGHT



Inspection Items
4.0 ATTIC, ROOF INTERIOR
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Picture 10
Picture 11
Comments: FOR YOUR INFORMATION
1,2,3,4,5,6,7,8,9,10,11-The wood members throughout the attic appeared free of moisture discoloration and deterioration. The insulation under readily accessible roof penetrations was scooped away in order to inspect the plasterboard ceilings. Overall attic construction is adequate with 2x6 rafters, 2x6 ceiling joists, sufficient purlin and collar-tie bracing boards, and the majority of the rafters are properly aligned onto the ridge and valley boards. This is good!

ACE Home Inspections, LLC is not responsible for any leakage within the attic that may be uncovered during a future storm because it was not raining at time of the attic inspection and only readily accessible areas are inspected and any conclusions are based solely on only what was inspected.
4.1 ATTIC, ROOF INTERIOR
Comments: FOR YOUR INFORMATION
1-All necessary attic areas have insulation with an R-value or resistance to heat loss value of R-30. This is good!
4.2 ATTIC, ROOF INTERIOR
Comments: FOR YOUR INFORMATION
1-Overall attic ventilation is adequate where air travels up through lower soffit vents and out through 3 upper gable vents and a center wind turbine. Soffit vents appeared clear or open and foam baffles are used where needed to keep air flows around insulation. This is good!
4.3 ATTIC, ROOF INTERIOR
Comments: FOR YOUR INFORMATION
GENERAL RECESSED LIGHT INFORMATION:

Basically recessed can lights consist of the recessed can housing, a lamp, and trim. They are required to be thermally protected with an internal thermostat switch. The power is cut if the temperature gets above a certain temperature, usually around 194 degrees. Once the temperature drops below a certain temperature, usually 184 degrees, the switch resets. However this does not guarantee complete safety. There are two types of fixtures, IC(insulated ceiling) type and Non-IC type. IC type fixture are usually safety rated for insulation. Non-IC rated fixtures have a warning label, "Warning, Risk of fire, Non-type IC only, Do not install insulation within 3 inches of sides or wiring compartment." This applies to all insulation because it retains heat causing items to possibly catch fire.

Non-IC rated fixtures can not have insulation within 3 inches. IC rated fixtures are permitted to be covered with insulation. ACE Home Inspections, LLC does not hunt for recessed can lights that are completely buried under insulation and are not readily accessible. Note that there are some circumstances where lighting is permitted to be covered with insulation when special trims are used. This is normally stated on the fixture by the manufacturer.

Opinions on this issue sometime vary among insulation installation contractors, however ACE Home Inspections, LLC has previously called several recessed light manufacturers, who all stated that whenever the sticker is present stating "keep all insulation 3 inches away" it MUST be kept 3 inches away and if a warning sticker is not present to check the interior side for any warning information along with a manufacturer and model number.

The determination of proper trim types is beyond the scope of the inspection. Verification can sometimes be as simple as a phone call to the manufacturer.
4.4 ATTIC, ROOF INTERIOR
Comments: MISCELLANEOUS INFORMATION
The attic has NO floor decking for storage, however is high clearance where floor decking which is properly secured to the ceiling joists would be recommended if storage is desired. It should be noted that the ceiling joists are 2x6, and are spaced 24 inches apart which is adequate but not robust where only a light duty storage would be recommended. (Maintenance tip.)
4.5 ATTIC, ROOF INTERIOR
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1-The hallway attic entry scuttle hole does not cete down flush in place because of two nails where nail removal is recommended.
4.6 ATTIC, ROOF INTERIOR
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The exhaust fan in each bathroom was found to be completely covered with insulation where they do NOT terminate properly to the exterior. Exhaust vents that terminate into the attic can cause excess moisture/humidity within the attic and possibly lead to moisture damaged ceiling plasterboard. A vinyl or metal flex hose can be ran from each fan to the closest gable or soffit vent. These kits are rather inexpensive and can be purchased at major home centers and are always recommended.
4.7 ATTIC, ROOF INTERIOR (Visible condition. Checking attic insulation, exposed wiring, lights and water pipes. Checking to see that all attic areas are accessible, all exposed sections of chimney in attic are free of soot and creosote leakage, that soffit vents are not covered with insulation, and attic ventilation vent screening which keeps animals out)
Comments: INSPECTED
4.8 GAS FLUE AND CHIMNEY FIRESTOPPING (Visible condition. Firestopping refers to size of the hole made in the ceiling and roof so as to maintain the proper clearance from a hot metal flue pipe or chimney brick.)
Comments: NOT PRESENT
4.9 DO ALL FLUES AND VENTS PRESENT IN ATTIC TERMINATE TO THE EXTERIOR (Water heater flue, furnace flue, metal chimney flue, plumbing vents, bathroom fan vents, range hood vent, dryer vent, etc...)
Comments: INSPECTED
4.10 RAFTERS, DECKING, JOISTS OR TRUSSES (Visible condition. Check for rafters pulling away from ridge board, rot, cracks, splits, cut, altered or missing supports.)
Comments: INSPECTED
4.11 IS ATTIC FREE OF VISIBLE ROOF LEAKS OR DETERIORATION (Flashing refers to materials, usually metal, that join parts of the house to the roof. Common places where roof leaks occur are flashings around chimneys, metal gas flues, plumbing vents, turbines, dormers, valleys, or any other roof penetrations or intersections.)
Comments: INSPECTED
4.12 IS ATTIC FREE OF VISIBLE CONDENSATION OR MOISTURE DAMAGE DUE TO IMPROPER VENTILATION (Often what appears to be a leak is in fact condensation, and a sign of inadequate ventilation. Proper attic ventilation reduces heat in summer and prevents condensation in winter. It allows air to carry off water vapor before it can condense and cause moisture damage.)
Comments: INSPECTED
4.13 INSTALLED MECHANICAL VENTILATION SYSTEMS (Visible condition and operation of power ventilators and fans)
Comments: INSPECTED

KITCHEN, BATHROOMS, INTERIOR ROOMS

Styles & Materials
REFRIGERATOR:
FRIGIDAIRE
DATED 08/2007
MEASURED REFRIGERATOR TEMP:
37 DEG
RANGE/COOKTOP BRAND:
FRIGIDAIRE
RANGE/COOKTOP ENERGY:
ELECTRIC
OVEN:
NORMAL UNDER COOKTOP
OVEN ENERGY:
ELECTRIC
BUILT-IN MICROWAVE:
FRIGIDAIRE
DATED JUNE 2007
RANGE HOOD:
PART OF MICROWAVE
HOOD EXHAUST:
RECYCLED EXHAUST
DISHWASHER:
FRIGIDAIRE
DISPOSER:
NONE
TRASH COMPACTORS:
NONE
INTERIOR CEILING MATERIALS:
PLASTERBOARD
INTERIOR WALL MATERIALS:
PLASTERBOARD
INTERIOR FLOOR MATERIALS:
CARPET
CERAMIC TILE
BATHROOMS:
2 FULL
BATHROOM INFO:
2 ONE-PIECE ACRYLIC TUBS
WITH A SHOWER
BATHROOM INFO:
FORMICA COVERED WOOD VANITIES
MASTER GLAZED WINDOW
EXHAUST FANS
KITCHEN SINK:
DUAL BASIN STAINLESS SINK
WINDOW OVER SINK
KITCHEN INFO:
EAT-IN KITCHEN
HANGING LIGHT FIXTURE
NO FORMAL DINING ROOM
REFRIGERATOR OPENING WIDTH:
39 INCHES
REFRIGERATOR OPENING HEIGHT:
72 INCHES
OTHER INTERIOR INFO:
12.78FT HIGH LIVING ROOM
LIVING ROOM STORAGE CLOSET



Inspection Items
5.0 KITCHEN, BATHROOMS, INTERIOR ROOMS
Picture 1
Picture 2
Picture 3
Picture 4
Picture 5
Picture 6
Picture 7
Picture 8
Picture 9
Comments: FOR YOUR INFORMATION
1,2,3,4,5,6,7,8,9-Each bathroom and kitchen sink basin was filled in order to pressurize the piping to inspect for leakage.
5.1 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: FOR YOUR INFORMATION
1-The refrigerator ice-maker and door dispenser units are functional. This is good!
5.2 KITCHEN, BATHROOMS, INTERIOR ROOMS
Picture 1
Picture 2
Picture 3
Comments: FOR YOUR INFORMATION
1,2-The stove and oven elements are functional. This is good!
5.3 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: FOR YOUR INFORMATION
The dishwasher was cycled and found functional and free of leakage. This is good!
5.4 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: FOR YOUR INFORMATION
The washer and dryer were cycled and found functional. This is good!
5.5 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: MISCELLANEOUS INFORMATION
The closet and laundry pantry have no installed shelving.

The bathroom mirrors were in-process of being installed at time of inspection.
5.6 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: MISCELLANEOUS INFORMATION
The stove and oven unit has excessive wobble where proper leveling or balancing to floor is recommended.
5.7 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: MISCELLANEOUS INFORMATION
The refrigerator has excessive wobble where proper leveling or balancing to floor is recommended.
5.8 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: MISCELLANEOUS INFORMATION
The living room ceiling fan has noticeable wobble on high speed where proper alignment or balancing is recommended.
5.9 KITCHEN, BATHROOMS, INTERIOR ROOMS
Picture 1
Picture 2
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1,2-The electrical receptacle to the right of the kitchen sink and another on the right exterior wall within the master bedroom are loose where they move around whenever a plug is inserted or removed. recommend both be properly secured where movement is prohibited.
5.10 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: FOR YOUR INFORMATION
ACE Home Inspections, LLC only tests a random sampling of house smoke alarms always recommends that ALL smoke alarms be tested and replaced if found defective before moving in. It is always recommended that a local fire department be contacted to determine where smoke alarms should be installed since each jurisdiction may have different standards.

Smoke alarms in this house are present in each bedroom and the laundry room off the kitchen.
5.11 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: FOR YOUR INFORMATION
ACE Home Inspections, LLC offers no warranties or guarantees. A home inspection is like a snap shot in time where component conditions are noted at the time of inspection. ACE Home Inspections, LLC is not responsible for component conditions occurring after the time of the inspection.
5.12 KITCHEN, BATHROOMS, INTERIOR ROOMS
Comments: FOR YOUR INFORMATION
ACE Home Inspections, LLC is not a licensed air quality, odor, or environmental expert and makes no conclusions as to any of the homes various odors or air quality other than noting any obvious apparent markings on floor coverings from normal wear and tear or from animals such as dogs, cats, or rodents. ACE Home Inspections, LLC always recommends used carpets be properly cleaned by a licensed carpet contractor and an air quality or environmental expert be contacted if client recognizes or concludes themselves that any apparent odors are present, before closing. ACE Home Inspections, LLC does not dismantle or open any non readily accessible areas such as air vents or ductwork and does not move objects or furniture and is not responsible for hidden or latent defects of any kind such as any cracked tile or torn and soiled carpet under furniture. ACE Home Inspections, LLC offers no warranties or guarantees and lists all conditions at the time of inspection, where the inspection is like a snapshot in time. For example a component proved to be in working order at time of inspection, could be malfunctioning soon after moving in at no fault of ACE Home Inspections, LLC.
5.13 KITCHEN (Visible condition of ceiling, walls, cabinets, shelving, countertops, plumbing. Checking that all outlets within six feet of sink have GFCI protection, and there are separate water shut-off valves for faucet, dishwasher, and ice-maker.)
Comments: INSPECTED
5.14 KITCHEN (Visible condition and operation of windows, doors, floor, cabinet doors, drawers, lights, switches, outlets, sink, faucet, spray nozzle and all appliances staying with house: range, oven, microwave, vent hood, dishwasher, disposal, refrigerator or any other appliances. Checking that sink and dishwasher drain properly, and hot and cold water pressure, volume, and temperature are adequate.)
Comments: INSPECTED
5.15 RANGE HOOD VENTING SYSTEM (If range hood is nonvented type, is there a clean charcoal or aluminum filter in place. A nonvented hood is for filtering odors and grease vapors and will not remove heat or steam like a vented range hood. A non-vented range hood is identified by louvers on the front of the hood and does not vent to exterior as a vented hood does.)
Comments: INSPECTED
5.16 ARE FAUCETS FREE OF HAMMERING AND VIBRATING NOISES WHEN TURNED ON/OFF RAPIDLY (This occurs when water flowing in the pipe comes to an abrupt stop, introducing shock and vibrations that can damage pipes or fittings. It is caused by improper sized pipes and can be fixed with an air chamber or antiknock coil which provides an air cushion to absorb shock.)
Comments: INSPECTED
5.17 DOES SINK DRAIN INTO A P-TRAP UNDER THE SINK (A trap is needed to provide a water seal that blocks sewer gases from seeping back into house. Some homes still have S-type traps that do not always vent properly. If a sucking and gurgling noise occurs after almost all the water has drained, the water seal has been lost. All S-traps should be converted to P-traps.)
Comments: INSPECTED
5.18 DOES SINK HAVE AN AIR GAP TO PREVENT BACK SIPHONAGE (Simply speaking, the air gap prevents the dirty sink water from being sucked back into the clean water supply pipes through the end of the faucet if the sink should overflow. There should be a gap of at least 1 inch between the end of the faucet where the water exits and the flood rim of the sink.)
Comments: INSPECTED
5.19 INTERIOR ROOMS (Visible condition of ceilings and walls.)
Comments: INSPECTED
5.20 INTERIOR ROOMS (Visible condition and operation of windows, doors, floors, lights, switches, outlets)
Comments: INSPECTED
5.21 BATHROOM (Visible condition of ceiling, walls, cabinets, countertops, and caulking.)
Comments: INSPECTED
5.22 BATHROOM (Visible condition and operation of windows, doors, floor, cabinet doors, drawers, exhaust fans, lights, switches, outlets, sinks, tubs, showers, and commodes. Checking presence of cut-off valves for faucets and commodes, proper draining of sinks, tubs, showers and commodes, use of P-traps and not old S-traps, proper air-gap for sinks, tubs, and hand-held shower wands to prevent back siphonage, faucets for improper hammering and vibrating noises when turned on/off rapidly, adequacy of hot and cold water pressure, volume, and temperature, exhaust fans for proper venting to building exterior and outlet GFCI protection.)
Comments: INSPECTED

PLUMBING (Main, Exterior, Water Heater, Washer, Dryer)

Styles & Materials
PLUMBING SUPPLY:
WIRSBO 3/4 TUBING
DISTRIBUTION:
WIRSBO CLEAR PEX TUBING
PLUMBING WASTE:
WHITE PVC(polyvinyl chloride) PIPING
WASTE SYSTEM:
UNKNOWN
WATER SOURCE:
PUBLIC/COUNTY
WATER HEATER BRAND/DATE:
AMERICAN
DATED 31ST WEEK OF 2007
WATER HEATER LOCATION:
CRAWLSPACE
WATER HEATER POWER SOURCE:
ELECTRIC
CAPACITY:
38 GAL
WATER FILTERS:
NONE OBSERVED
DRYER POWER SOURCE:
240 ELECTRIC
WATER CUT-OFF:
CRAWLSPACE
AT STREET
BATHROOM SINK PLUMBING:
WHITE PVC(polyvinyl chloride) PIPING
WIRSBO TUBING
KITCHEN SINK PLUMBING:
WHITE PVC(polyvinyl chloride) PIPING
WIRSBO TUBING
WASHER:
FRIGIDAIRE
CYCLED OKAY
DRYER:
FRIGIDAIRE
CYCLED OKAY



Inspection Items
6.0 PLUMBING SYSTEM
Comments: FOR YOUR INFORMATION
1-House water cut-offs are located at street and on crawlspace ceiling near the right side entry door. A pressure regulator also exists along the ceiling and can be used to adjust house water pressure. Water pressure appeared adequate and should not need to be adjusted. This is good!
6.1 PLUMBING SYSTEM
Picture 1
Picture 2
Picture 3
Picture 4
Comments: MISCELLANEOUS INFORMATION
1,2,3,4-This house utilizes Wirsbo AQUAPEX water tubing lines instead of rigid copper tubing pipes. Wirsbo AQUAPEX tubing is a cross-linked polyethylene which makes it extremely flexible, durable and able to withstand high temperatures and pressures. The AQUAPEX tubing and a PEX ring compress over the PROPEX fitting for a connection that is permanent, leakproof, and reliable. AQUAPEX tubing has been used around the world for over 25 years. Its unique properties give it many advantages over rigid metal and other plastic plumbing systems. AQUAPEX is corrosion resistant, unlike copper and it is more freeze resistant. It is also flexible, thus eliminating many of the joints that used in rigid copper or metal systems.

According to the manufacturer, it is rare that Wirsbo tubing will burst as traditional copper piping does when temperatures get below freezing. It is normally good down to 0 degrees and should not burst even though the water in the line freezes, however the concern is NOT about bursting pipes, but water service. RAUPEX recommends that potable or drinking water piping not be placed in areas where temperatures get below 40 degrees because if the water freezes in the tubing, then water flow is gone and nothing will come out of the faucets. It is always recommended, but NOT required, that all Wirsbo water tubing be covered with insulation. (Maintenance tip.)

It appears that all Wirsbo water piping in this house is located throughout the crawlspace and not within the attic. If within the attic then it would be covered with insulation, however since it is all within the crawlspace, and not covered with insulation, there could be rare instances when freezing or water flow restriction could occur?

ACE Home Inspections, LLC lists this information as a courtesy and does not endorse any type of water piping, with the only intent being to give additional information which was obtained from the product manufacturer.
6.2 PLUMBING SYSTEM
Comments: MISCELLANEOUS INFORMATION
1-The electric water heater is functional. Tank size, however is only 38 gallon, which may be adequate, however if a robust or a prolonged amount of hot water will be required then a larger tank may be desired.

Standard Water Heater Sizing

Number of Bathrooms 1 to 1.5 / 2 to 2.5 / 3 to 3.5

Number of Bedrooms 1 2 3 / 2 3 4 5 / 3 4 5 6

Nominal Tank Size 20 30 40 / 50 50 50 66 / 50 66 66 80


*****Based on above chart this 2 bathroom, 3 bedroom home would require a 50 gallon tank.

6.3 PLUMBING SYSTEM
Picture 1
Picture 2
Comments: MISCELLANEOUS INFORMATION
1-----UPGRADE-----Washer hoses that are original black hose type are susceptible to sudden leaking. It is always recommended, but not required, that new wire braided permanent type hoses be installed like the ones shown. These can be purchased at major home and appliance centers and are relatively inexpensive. (Maintenance tip.)

Present hoses in this house are black rubber where replacement with robust wire braided hoses is recommended, but is NOT required.
6.4 PLUMBING SYSTEM
Comments: FOR YOUR INFORMATION
1-The two hose bibs have been made more rigid and less susceptible to damage through the installation of a small section of copper tubing through the foundation walls, as shown. This is good!
6.5 PLUMBING SYSTEM
Comments: FOR YOUR INFORMATION
There was no potable water expansion tank observed which are always recommended but are NOT required. Water piping is Wirsbo plastic tubing which is less susceptible to damage from jumping from sudden bursts of water pressure, however a water expansion tank can only make the entire system more robust which is it is alwys recommended, even though it is not required. (Maintenance tip.)

ADDITIONAL EXPANSION TANK INFORMATION:

A potable water expansion tank is always recommended, but not required between the cold water line and the water pressure reducing valve. It is designed to absorb thermal expansion and to maintain balanced pressure throughout the potable water supply system. Heated water expands and in a domestic hot water system the system may be closed when isolated by a pressure reducing valve. Provisions should be made for this expansion. The expansion tank absorbs the increased volume of water created when the hot water storage tank is heated and keeps the system pressure below the relief setting of the T & P relief valve. It is a pre-pressurized steel tank with an expansion membrane that prevents contact of water with the air in the tank. This prevents loss of air to the water and ensures a longer system life. The tank has a polypropylene liner, butyl diaphragm and a field adjustable pre-charge. Refer to sample picture.
6.6 PLUMBING SYSTEM
Picture 1
Picture 2
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2-Both exterior hose bibs are missing a bacflow preventer. They are relatively inexoensive and can be purchase at major home centers. Even if determined not to be required in the jurisdiction where the house is constructed, they are always recommended for safety reasons.

ADDITIONAL BACFLOW PREVENTER INFORMATION:

1-The simplest backflow protection is the simple air gap between the end of a sink faucet where the water exits and the flood rim of the sink as explained in the bathroom section. Another place where backflow protection is needed is on outside hose bibs or faucets. This involves purchasing a relatively inexpensive backflow preventer that easily screws on to the end of the faucet that will allow water to flow in only one direction, out of your faucet. This prevents any contaminated water in your hose from being sucked back through the house water supply. It is recommended that all hose bibs have a backflow preventer such as one shown in picture 2.
6.7 PLUMBING SYSTEM
Comments: MINOR REPAIRS, (REFER TO REPORT PICTURES)
1-The water heater side mounted TPR valve does not have a 3/4 inch sized extension pipe ran to within 6 inches of the floor. Extension pipes are always recommended for all water haters, wherever they are located. (safety)

ADDITIONAL TPR VALVE INFORMATION:

Water heaters have a TPR valve (Temperature Pressure Relief) or T&P valve, which is a safety device that releases pressure if the pressure or the temperature reach an unsafe level. All tank type units must have a TPR valve, otherwise they could blow up. The purpose of the TPR valve is to provide an important safety mechanism that allows for the immediate discharge of excess temperature and pressure that builds up inside the tank as the water is heated. Due to the scalding potential of the discharge from the TPR valve, the outlet from the valve should be piped to a safe area. Typically TPR valve discharges are piped down to within 6 inches of the floor or outside of the dwelling at near ground level. A TPR Valve that has been fitted with a discharge pipe that is smaller than the size of the valve outlet is a common defect that is strictly prohibited because smaller discharge pipes restrict the flow of the pressurized water released by the valve. This creates a dangerous bottleneck, building-up even more pressure at the point of discharge that can cause the tank to explode. Personal injury (or death) and property damage may result. The discharge pipe must be made of a material that's rated for both high temperature and pressure. This includes most rigid wall copper, iron and, in most places, chlorinated polyvinylchloride (CPVC plastic not regular PVC) pipe. The pipe size must match the opening size of the TPR valve discharge (usually : inch). It must terminate 6"-12" above the floor, and the end cannot be threaded or have a fitting which permits connecting a plug or cap.
6.8 WATER HEATER, PTV - PRESSURE TEMPERATURE VALVE, PTV DRAIN PIPING (Visible condition. Checking presence of a drain pan under unit if installed in attic or room over a living area, and presence of a cold water inlet water cut-off valve.)
Comments: INSPECTED
6.9 ELECTRIC WATER HEATER EXTERIOR TANK WIRING AND ELEMENT COVERS (Visible condition.)
Comments: INSPECTED
6.10 EXPOSED INTERIOR WATER PIPING (Visible condition, looking for leaks, corrosion, sagging sections, and valves where it enters house and stops at the point where it enters rooms where it then will be described in each rooms description in this report.)
Comments: INSPECTED
6.11 EXTERIOR HOSE FAUCETS, WATER PRESSURE, WATER VOLUME, WATER DRAINS (Visible condition and operation. Checking for presence of faucet backflow preventers.)
Comments: INSPECTED
6.12 CLOTHES WASHER WATER CONNECTIONS, DRAIN PIPE, AND HOSES (Visible condition.)
Comments: INSPECTED
6.13 ELECTRIC CLOTHES DRYER OUTLET OR GAS CLOTHES DRYER CONNECTION (Visible condition. Checking dryer exhaust vent for exterior building termination and exterior cover with functional flap.)
Comments: INSPECTED
6.14 DRAINAGE SUMPS, SUMP PUMPS, AND RELATED PIPING (Visible condition and operation, checking any switches, valves, piping, and for any debris. Sump pumps are used to remove ground water and/or surface water from the house.)
Comments: NOT PRESENT

ELECTRICAL (Service, Interior Distribution Panels, Exterior)

Styles & Materials
SERVICE DROP TO HOUSE:
ABOVE GROUND
USES A DRIP LOOP
ATTACHES TO A MAST
ATTACHES TO SIDING
MAIN PANEL TYPE:
CIRCUIT BREAKERS
WIRING METHODS:
ROMEX
15 AND 20 AMP CIRCUIT TYPE:
COPPER
MAIN HOUSE POWER DISCONNECT:
RATED 200 AMP
IN MAIN PANEL
CUTS ALL POWER
MAIN HOUSE PANEL CAPACITY:
200 AMP
MAIN HOUSE PANEL LOCATION:
LAUNDRY ROOM
MAIN HOUSE PANEL MANUFACTURER:
SQUARE D
HOUSE BREAKERS:
SQUARE D



Inspection Items
7.0 ELECTRICAL SYSTEM
Picture 1
Picture 2
Comments: FOR YOUR INFORMATION
1,2-The main electrical panel appeared free of discoloration, corrosion, and deterioration. This is good! Please see rest of electrical section for all items inspected.
7.1 ELECTRICAL SYSTEM
Comments: FOR YOUR INFORMATION
ACE Home Inspections, LLC does not inspect lighting controlled by timers, and photo or motion type detectors and only tests a random sampling of the exterior lighting.
7.2 ELECTRICAL SYSTEM
Comments: FOR YOUR INFORMATION
1-The electrical system is grounded to aground water. This is good! The water piping is Wirsbo plastic tubing which does not require grounding.
7.3 ELECTRICAL SYSTEM
Comments: FOR YOUR INFORMATION
1-The 240 volt dryer receptacle appears adequate and is functional. This is good!
7.4 ELECTRICAL SYSTEM
Comments: MISCELLANEOUS INFORMATION
1-The service entry cable appears adequate, however travels through the tree limbs where periodic trimming maintenance is recommended. (Maintenance tip.)
7.5 ELECTRICAL SYSTEM
Picture 1
Picture 2
Picture 3
Comments: MISCELLANEOUS INFORMATION, (REFER TO REPORT PICTURES)
1,2,3-All outlets were tested with a SureTest outlet tester and found to have proper voltage and grounding. GFCI protected outlets were observed in bathrooms, kitchen, and exterior outlets. This is good!

(GFCI issue) The rear deck is GFCI protected through the left side hallway bathroom GFCI type outlet. The front porch outlets are GFCI protected through the master bathroom GFCI type outlet. This is functional, however is no longer an acceptable new construction method where all bathrooms outlets should have their own isolated GFCI protection, and all kitchen outlets within six feet of a sink basin should have their own isolated GFCI protection. Only exterior, garage and basement outlets are allowed to still be tied together with the same GFCI protection. This may not be required within the jurisdiction where the house was constructed, where builder may not be required to isolate, however is always recommended.

(AFCI issue) Since this house was constructed after January 1, 2002 it is required by the National Electrical Code to have proper AFCI protected bedroom outlets. Normally each bedroom will have an AFCI type breaker in the electrical panel that has a green or blue reset button. No AFCI protection was observed at time of the inspection. These may not be required within the jurisdiction where the house was constructed, where builder may not be required to install, however are always recommended.

Opinions by licensed electrical contractors on this issue may vary where contacting. There are hundreds of various jurisdictions throughout the state of Alabama. The knowing of each's specific rules or codes is beyond the scope of the inspection, where the contacting of the local jurisdiction is always recommended, and correcting if required.

Remember that breakers are only designed to protect the wiring, while a GFCI and AFCI are designed to protect you!

GENERAL GFCI AND AFCI INFORMATION:

A GFCI or Ground-Fault-Circuit Interrupter is a device intended for the protection of personnel that functions to de-energize a circuit within an established period of time when a current to ground exceeds the values established for a Class A device. Class A ground-fault circuit interrupters trip when the current to ground has a value in the range of 4ma (milli-amps) to 6ma (milli-amps). All outlets within 6 feet of any water source, whirlpool tubs, hot tubs, swimming pools, unfinished basement or crawlspace,